Customization: | Available |
---|---|
Application: | Power, Electronic, Instrument, Lighting, Rectifier, Audio |
Phase: | Three |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
S11/S13 series oil immersed distribution transformers use insulating oil as cooling and insulating medium.The core is made of high quality cold rolled sillcon steel, the oil tank adopts corrugated oil tank without oil conservaor.Vacuum oilinjection process is adopted to effectively prevent oxygen and water from penetrating into transformer oilresulting in the decline of insulating oil performance.It is a new generation of energy-saving and environmental protection products.
Rated capacity (kVA) |
Voltage combination | Join group label |
No-load loss(W) | Load loss (W) |
No-load current (%) |
Short circuit impedance (%) |
||
high pressure (kV) |
High pressure tap range(%) |
Low pressure (kV) |
||||||
30 | 11 10.5 10 6.3 6 |
±5±2×2.5% |
0.4
0.69 |
Yyn0 Dyn11 | 100 | 630/600 | 2.3 | 4 |
50 | 130 | 910/870 | 2.0 | 4 | ||||
63 | 150 | 1090/1040 | 1.9 | 4 | ||||
80 | 180 | 1310/1250 | 1.9 | 4 | ||||
100 | 200 | 1580/1500 | 1.8 | 4 | ||||
125 | 240 | 1890/1800 | 1.7 | 4 | ||||
160 | 280 | 2310/2200 | 1.6 | 4 | ||||
200 | 340 | 2730/2600 | 1.5 | 4 | ||||
250 | 400 | 3200/3050 | 1.4 | 4 | ||||
315 | 480 | 3830/3650 | 1.4 | 4 | ||||
400 | 570 | 4520/4300 | 1.3 | 4 | ||||
500 | 680 | 5410/5150 | 1.2 | 4 | ||||
630 | 810 | 6200 | 1.1 | 4.5 | ||||
800 | 960 | 7500 | 1.0 | 4.5 | ||||
1000 | 1150 | 10300 | 1.0 | 4.5 | ||||
1250 | 1360 | 12000 | 0.9 | 4.5 | ||||
1600 | 1640 | 14500 | 0.8 | 4.5 | ||||
2000 | 1960 | 19800 | 0.8 | 5 | ||||
2500 | 2310 | 23000 | 0.7 | 5 |
Rated capacity (kVA) |
Voltage combination | Join group label |
No-load loss(W) | Load loss (W) |
No-load current (%) |
Short circuit impedance (%) |
||
high pressure (kV) |
High pressure tap range(%) |
Low pressure (kV) |
||||||
50 | 20 22 24 |
±5±2×2.5% | 0.4 | Dyn11 Yyn0 | 170 | 1270/1210 | 2.00 | 6.5 |
100 | 230 | 2120/2020 | 1.80 | 6.5 | ||||
125 | 270 | 2500/2380 | 1.70 | 6.5 | ||||
160 | 290 | 2970/2830 | 1.60 | 6.5 | ||||
200 | 340 | 3500/3330 | 1.50 | 6.5 | ||||
250 | 410 | 4160/3960 | 1.40 | 6.5 | ||||
315 | 490 | 5010/4770 | 1.40 | 6.5 | ||||
400 | 580 | 6050/5760 | 1.30 | 6.5 | ||||
500 | 690 | 7280/6930 | 1.20 | 6.5 | ||||
630 | 830 | 8280 | 1.10 | 6.5 | ||||
800 | 980 | 9900 | 1.00 | 6.5 | ||||
1000 | 1150 | 12150 | 1.00 | 6.5 | ||||
1250 | 1410 | 14670 | 0.90 | 6.5 | ||||
1600 | 1700 | 17550 | 0.80 | 6.5 |